1) Tap on the grey bar at the top middle of the screen
2) Tap Settings
3) Tap Advanced Settings
4) Enter Dealer Code (Default 2222)
5) Tap Installation
6) Tap Dealer Settings
7) Tap EN Grade 2 To enable/disable
What is EN Grade 2:
- Entry Procedure (EU) - follows entry procedures and alarm transmission delays specified by EN
50131
- Disables the “Auto Bypass” setting so that the Panel will protest arming when sensor and panel
trouble conditions are present (i.e. Open, Tamper, Low Battery, etc)
- Trouble condition alerts can not be acknowledged until the condition is resolved
- Trouble beeps are expanded to include fault indications required by EN 50131
- “Screen Lock” setting is enabled automatically. Screen will lock 30 seconds after Disarming
- A new icon called “EU Events” is added to the “Settings" page which records mandatory history
events specified by EN 50131.
- “Loss of Supervisory Signals for PowerG Non-Emergency Sensors” is set to 2 hours by default.
- “LED Indicator” setting is Disabled automatically.
- “Partitions” setting is not available.
- “Dealer or Installer Access Requires User Permission” setting is Enabled automatically.